Air Cooled Turbogenerators - general characteristics
Generators have indirect cooled stator windings and direct cooled rotor windings.
Stator core is direct cooled with air.

Frequency Hz Speed RPM Power factor Rated Voltage kV Power Range MVA
50 3000 0,8 10,5 - 16 20 - 210
50 3000 0,8 15 - 20 210 - 350
60 3600 0,85 13,8 - 18 30 - 230
60 3600 0,85 17 - 21 230 - 300
Mounting arrangement IM7305, IM7315, IM7316
Method of cooling: IC 9 A1 W7 - IC 8 A1 W7
Protection degree: IP 54 (IEC 60034-5)
Excitation: static (standard) or brushless as special application
Thermal insulation class: F; thermally loaded only to class B
Terminal location: - above 3 + 3
- below, for connection to the bus duct in the foundation
Coolers arrangement: - in the lower part of the frame
- in the foundation
Installation: with soundproof enclosure for indoor or outdoor application


Hydrogen Cooled Turbogenerators general characteristics
Generators have indirect cooled stator windings and direct cooled rotor windings. Hydrogen is used as a
coolant fluid. Stator core is direct cooled with hydrogen.

Frequency Hz Speed RPM Power factor Rated Voltage kV Power Range MVA
50/60 3000/3600 0,8 - 0,9 up to 21 up to 600
Mounting arrangement IM1105, IM1106, IM7305
Method of cooling: IC 8 (H1) W7
IC 8 H1 W7 stat. winding
Protection degree: IP 54 (IEC 60034-5)
Excitation: static (standard) or brushless as special application
Hydrogen pressure: 4 - 7 bar
Thermal insulation class: F; thermally loaded only to class B
Terminal location: 3 above + 3 below
Installation: indoor or outdoor


Hydrogen - Stator Water cooled Turbogenerators general characteristics
Generators have direct cooled stator windings through demineralized water and direct cooled rotor windings
with hydrogen. Stator core is direct cooled with hydrogen.

Frequency Hz Speed RPM Power factor Rated Voltage kV Power Range MVA
50/60 3000/3600 0,8 - 0,9 18 - 27 400 - 900
Mounting arrangement IM7305
Method of cooling: IC 8 (H1) W7
IC 9 (W7) W7 stat. winding
Protection degree: IP 54 (IEC 60034-5)
Excitation: static
Hydrogen pressure: 3 - 6 bar
Thermal insulation class: F; thermally loaded only to class B
Terminal location: 6 below
Installation: indoor or outdoor




Top
Power Plants
Components
Gas Turbines
Steam Turbines
Turbogenerators
Features
References
Photogallery
Hydrogenerators
Engineering capabilities
Service
E-business

Search
Go

   Download Download
Turbogenerators (pdf 1.8 Mb)

Download Acrobat Reader Acrobat Reader
 
Site Map|Accessibility|Privacy|Credits